When a corrosive chemical splashes into someone’s eyes or onto their skin, the first seconds decide how serious the injury becomes. Emergency safety showers and eyewash stations exist to start flushing immediately, before medical help arrives. ANSI/ISEA Z358.1, the American National Standard for emergency eyewash and shower equipment, is the reference most widely used by laboratories, consultants and safety auditors in the UAE and across the GCC. This guide summarises its key requirements for placement, performance and testing, based on the 2014 edition. Always check the current edition and any local authority requirements for your project.
Types of emergency equipment
- Emergency shower: a showerhead delivering a large volume of water over the whole body.
- Eyewash: flushes both eyes at the same time with a gentle, controlled flow.
- Eye/face wash: a larger unit that flushes the eyes and face together.
- Combination unit: a shower and eyewash (or eye/face wash) on one frame, common in labs and plant areas.
- Drench hose: a hand-held supplementary unit. It supports, but does not replace, a primary eyewash or shower.
Plumbed units are connected to the water supply; self-contained units carry their own flushing fluid and must be refilled or replaced on schedule. See our safety showers and eyewash stations for plumbed and combination models.
Flow and duration requirements
ANSI Z358.1 requires a 15-minute flushing period for all types. The minimum flow rates are:
- Emergency shower: at least 75.7 litres per minute (20 US gallons per minute) at 2.1 bar (30 psi)
- Eyewash: at least 1.5 litres per minute (0.4 gpm) at 2.1 bar (30 psi)
- Eye/face wash: at least 11.4 litres per minute (3 gpm) at 2.1 bar (30 psi)
That means a single shower can use over 1,100 litres in a full flush. The supply pipework must be sized for it, and the area needs a plan for where the water goes, whether a floor drain or a containment arrangement where contaminated run-off must be collected.
Where to put them: the 10-second rule
The standard requires equipment to be reachable within 10 seconds, which is generally taken as about 16.8 metres (55 feet) of walking distance for an unimpaired person. In practice:
- Install units on the same level as the hazard, with no stairs, ramps or doors that could slow an injured person. A door is allowed only if it opens in the direction of travel and has no lock.
- Keep the route clear of obstructions at all times. Storage creeping into the path is one of the most common audit findings.
- Where strong acids, strong caustics or other highly corrosive chemicals are handled, place the unit immediately next to the hazard; the standard’s guidance recommends this and a safety professional should confirm it.
- Mark the location with a highly visible sign and keep the area well lit.
- Do not install units where flushing water could hit electrical equipment or create a further hazard.
Installation heights and clearances
- Shower head: the water column should begin between 208 cm and 244 cm (82–96 inches) above the floor where the user stands.
- Spray pattern: at least 50.8 cm (20 inches) in diameter at 152.4 cm (60 inches) above the floor.
- Clearance: the centre of the shower spray should be at least 40.6 cm (16 inches) from any obstruction.
- Eyewash nozzles: between 83.8 cm and 134.6 cm (33–53 inches) above the floor, and at least 15.3 cm (6 inches) from the wall or nearest obstruction.
- Shower valve actuator: no more than 173.3 cm (69 inches) above the floor, easy to find and operate.
Activation and hands-free operation
The control valve must go from off to on in one second or less, and must stay open without the user holding it, so both hands are free to hold the eyes open or remove contaminated clothing. Eyewash nozzles need protective covers to keep out dust, and the covers must come off automatically when the unit is activated.
Tepid water: a particular issue in the GCC
ANSI Z358.1 requires flushing fluid to be tepid, defined as between 16°C and 38°C (60–100°F). Water that is too cold discourages people from completing the 15-minute flush; water that is too hot can increase chemical absorption and injury. In the UAE, Oman, Qatar and Saudi Arabia, the challenge is usually heat: water standing in exposed pipes, rooftop tanks or outdoor units can exceed 38°C in summer. Solutions include insulating and shading supply pipes, routing them inside conditioned spaces, using thermostatic mixing valves with chilled or tempered supply, and selecting units designed for hot climates. Check the water temperature at the outlet during the hottest months, not just at commissioning.
Weekly activation and annual inspection
- Weekly: activate plumbed units long enough to confirm water flows and to flush the line of stagnant water and sediment. This also reduces the risk of bacterial growth in dead legs.
- Self-contained units: check fluid levels and expiry dates as the manufacturer specifies.
- Annually: inspect every unit against the full requirements of the standard, including flow rate, spray pattern, height, temperature, signage, access route and valve operation.
- Keep a tag or log at each unit recording who tested it and when.
Linking with other lab safety systems
Emergency showers and eyewash stations are the last line of defence. They work alongside engineering controls such as fume hoods and spot extractors, proper chemical and gas cylinder storage, and a gas detection system for hazardous gases. Some facilities add a flow switch to each shower so that activation raises an alarm at a security desk or on the building management system, making sure someone comes to help.
Quick checklist
- Hazard assessment done; unit type selected for each area
- Reachable within 10 seconds on the same level, route kept clear
- Supply pipe sized for full flow for 15 minutes; drainage planned
- Tepid water confirmed at the outlet in summer conditions
- Heights, clearances and hands-free valves checked
- Signage and lighting in place
- Weekly activation and annual inspection scheduled and logged
- Staff trained to use the equipment and to help a colleague